Non-standard electric equipment up to
|
Thermal heated explosion-proof cases of KShO-E type
Symbolic notation structure of КShО-E
Operating conditions КShО-E are intended for operation in potentially explosive environment, in premises of В-1a, В‑1g classes (according to PUE, ch.7.3) not containing current-conducting dust, in which formation of explosive mixes of gases and vapors with air of II, II-А, II-В, II-С categories of Е1‑Е4 groups in accordance with GOST Р 51330.13-99 is possible. UHL climatic modification of installation category 1 is in accordance with GOST 15150-69. Air temperature is from minus 60°С up to plus 45°С, with the temperature inside a casing, at temperature regulator being switched on, not lower than plus 5°С. Height above sea level is up to 1000 m. Explosion-proof level 2 of КShО-E (increased explosion-proof reliability) is provided with application of built-in electric equipment of corresponding explosion protection types and levels. In КShО-E the following equipment can be installed:
Design and actionStructurally KshO-E metal jacket is two-layer with heat-insulating material filling. Basic KshO-E sizes are given in table 1.4.As a source of heat inside a case electric radiator is installed. Rate of KShO-E protection is IP54 in accordance with GOST 14254-96. Doors are gasketed with cold-resistant rubber. |
|